Separator Type HEPA Filters
Material Overview
- Deep Pleated
- Low pressure drop with high capacity
- Available in varieties of cell sides and efficiencies
- All HEPA filter efficiency is tested in accordance with
EN 1822 - Available standard (STD series) and High (HI series) capacity series
Application
- Used as final filter in hospital, pharmaceutical and food processing industry
Standard
- EN1822:2009 : H13, H14
- Filter Depth (Inches) : 12″
- Media Type : Glass Fibre
- Frame Material : Galvanized Steel (Standard), Stainless Steel, Aluminum, Plywood
- Separator Style : Aluminum
- Gasket Material : PU, Neoprene, EPDM, RB
- Gasket Position : Downstream, Upstream, Both sides
- Header Type : Single Flange, Double Flange, Box Type
- Rec. Final Resistance : 2x Initial pressure drop
- Max Operating Temperature : 70°C
Introduction
Model | Nominal Size Inches (H x W x D) |
Actual Size mm (H x W x D) |
Rated Airflow (CMH) |
Rated Initial Resistance (Pa) |
H13 Classfication | ||||
BA | 12 x 24 x 12 | 305 x 610 x 290 | 850 | 250 |
24 x 24 x 12 | 610 x 610 x 290 | 1,700 | ||
H14 Classfication | ||||
BA | 12 x 24 x 12 | 305 x 610 x 290 | 850 | 250 |
24 x 24 x 12 | 610 x 610 x 290 | 1,700 | ||
H13 Classfication (HI) | ||||
BA | 12 x 24 x 12 | 305 x 610 x 290 | 1,700 | 350 |
24 x 24 x 12 | 610 x 610 x 290 | 3,400 | ||
H14 Classfication (HI) | ||||
BA | 12 x 24 x 12 | 305 x 610 x 290 | 1,700 | 350 |
24 x 24 x 12 | 610 x 610 x 290 | 3,400 |
* Other dimensions are available on request *
Initial Resistance vs. Airflow